Coleman PM402511 Portable Generator User Manual


 
NOTE: The generator frame has been designed with
rectangular slots and frame tubes to be used
with a forklift for removing the unit from the
pallet and positioning the unit on the cement
pad.
NOTE: The generator has an engine fan that draws the
air in from the side panel slots, circulates it within
the enclosure and forces the air through the
radiator and out the lid on the exhaust outlet side
of the unit.
For proper ventilation and maintenance, locate the
generator outdoors in an area that will allow a minimum
of four feet of clearance between the generator and any
other structure.
When placing the generator, the direction of the
exhaust should be pointing away from windows, doors
and any ventilation system.
Insure that sufficient air flow is available to remove
the exhaust fumes and cool the generator properly.
The generator should be installed with masonry
anchor bolts on a level wire reinforced cement pad that is
4-6 inches thick and extends a minimum of 6” around all
sided of the unit.
NOTE: It would be extremely difficult, if not impractical,
to attempt a detailed coverage of every
installation possibility. For that reason, much of
the information is general in nature. Plan the
installation carefully. Information in this manual is
provided as a guide only and is not meant to
serve as a detailed installation plan. Illustrations
provided in the manual must not be construed as
blueprints.
All local applicable codes, standards and regulations
must be followed for the installation of the generator.
Some areas may require building permits and/or detailed
sight inspections prior to approving the unit for use.
NOTE: Utility wiring from the house to power the
battery charger and other start assisting
components should be tightened on the
identified terminal block at a torque of 20 lb-
in. The wire size is to be selected according
to allowable ampacities given in Table 310-16
of the National Electric Code.
Signal wiring from the transfer switch is to be
18AWG multi-strand wire tightened on the
identified terminal block to a torque of 20 lb-
in.
Power leads from the generator/circuit
breaker being wired to the transfer switch
should be tightened in the identified terminal
block to 120 lb-in. The wire size is to be
selected according to allowable ampacities
given in Table 310-16 of the National Electric
Code.
Field wiring of this unit must be conducted
by a licensed electrician.
CCAAUUTTIIOONN
Covering or restricting the air passages on the
generator will cause the unit to overheat and
may create a fire hazard. Do not allow snow or
leaves to cover enclosure openings.
Leave a four foot open area around all sides of
the unit. Do not plant trees or plants which may
grow within four feet of the unit.
Unit should be located such that it prevents
combustible material from accumulating under
the generator set.
The generator MUST be installed outdoors.
L
L
O
O
C
C
A
A
T
T
I
I
O
O
N
N
A
A
N
N
D
D
G
G
E
E
N
N
E
E
R
R
A
A
T
T
O
O
R
R
P
P
L
L
A
A
C
C
E
E
M
M
E
E
N
N
T
T
I
I
N
N
S
S
T
T
A
A
L
L
L
L
A
A
T
T
I
I
O
O
N
N
DDAANNGGEERR
Improper installation can damage your
electrical system and cause property damage,
serious personal injury or death. Installation
MUST be performed by a licensed electrician
and plumber, or gas technician and installation
MUST comply with all applicable building and
electrical codes. Some areas may require
building permits and/or detailed sight
inspections prior to approving the unit for
operation.
WWAARRNNIINNGG
Hazardous voltage can cause severe injury or
death. Electrocution is possible whenever
electricity is present. Open the main circuit
breaker of all power sources before servicing
the equipment. Configure the installation to
electrically ground the generator set, transfer
switch and related equipment and electrical
circuits to comply with applicable codes and
standards. Never contact electrical leads or
appliances when standing in water or on wet
ground because these conditions increase the
risk of electrocution.
When lifting the generator or using hoisting
equipment, be careful not to touch overhead
power lines. Proper tools and equipment and
qualified personnel should be used in all
phases of handling and unpacking.
This generator has an open bottom and must be
mounted on a cement pad.
The exhaust from this product is extremely hot
and remains hot after shutdown. High grass,
weeds, brush, leaves, or other combustible
materials, must remain clear of the exhaust.
Such materials may ignite and burn from the
heat of the exhaust system.
8