Electrical Specifications
60 Pound Capacity Models
Voltage Designation Standard Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load
Amps
Circuit
Breaker
AWG
mm
2
Full Load
Amps
Circuit
Breaker
AWG
mm
2
2 Speed and Fixed-Speed Models
C 380-415 50 3 4 5 15 14 2.5 27 30 10 6.0
F 440-480 60 3 3 5 15 14 2.5 24 30 10 6.0
J 200 50 3 3 10 20 12 4.0 N/A
O 208-240 60 3 3 10 20 12 4.0 48 50 8 10.0
Variable-Speed Models
R
(through
7/6/10)
380-480 50/60 3 3 6 15 14 2.5 23 30 10 6.0
N
(starting
7/7/10)
440 – 480 60 3 3 6 15 14 2.5 24 30 10 6.0
P
(starting
7/7/10)
380 – 415 50 3 3 6 15 14 2.5 24 30 10 6.0
Q 200-240 50/60 3 3 8 15 14 2.5 43 50 8 10.0
X 200-240 50/60 1/3 2/3 11/8 15 14 2.5 N/A
NOTE: Wire sizes shown are for copper, THHN, 90°C conductor per NEC article 310.