Xantrex Technology power Inverter Stacking Portable Generator User Manual


 
Installation
2–16 975-0059-01-01 Rev A
Connecting the ISC-S Cable
The ISC-S Cable connects to the Stacking Port on the AC end of the Sine Wave
Plus Inverter/charger. The Stacking Port is a 25-pin receptacle for the 25-pin
D-connector on the ISC-S Cable. Once the connector is in place, it is secured by
two screws on the sides of the connector.
To connect the ISC-S cable:
1. Orient the 25-pin D-connector to align with the Stacking Port on the Inverter
and gently press the connector into the port. Use caution not to bend the pins
inside the connector head.
2. Tighten the screws on the connector to secure the cable to the port.
3. Connect the other end of the ISC-S cable to the second inverter’s Stacking
Port as instructed in step 1 and 2.
Figure 2-8
The 25-pin D-connector on the ISC-S Cable
Figure 2-9
Stacking Port Locations on SW Plus Inverters
Align the head of the connector
with the Stacking Port on the
inverter and insert into the port.
Gently tighten these two screws to
secure in place.
Stacking Port