Murphy A900 Series Portable Generator User Manual


 
Table 7-2.1
22
Mode
Selector
OFF
Mode Selector
AUTO
Stand-by
Mode Selector
AUTO
Cranking
Mode Selector
AUTO
Running
Mode Selector
AUTO
Shutdown
Input
Voltage
Input
Voltage
Input
Voltage
Input Voltage Input
Voltage
13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
1 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
4 0000000000
5 13.8 27.6 13.8 27.6 0 0 0 0 13.8 27.6
6 0 0 0 0 13.8 27.6 13.8 27.6 0 0
7 13.8 27.6 13.8 27.6 0 0 0 0 13.8 27.6
8 0 0 0 0 13.8 27.6 13.8 27.6 0 0
9 0 0 0 0 0 0 0 0 13.8 27.6
10 0 0 0 0 0 0 0 0 13.8 27.6
11 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
12 13.8 27.6 0 0 0 0 0 0 0 0
13 13.8 27.6 0 0 0 0 0 0 13.8 27.6
14 0000000000
15 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
16 6666660066
17 .3 .3 .3 .3 13.8 27.6 .3 .3 .3 .3
18 0 0 0 0 13.8 27.6 0 0 0 0
19 13.8 27.6 13.8 27.6 1.5 1.5 1.5 1.5 13.8 27.6
20 0 0 13.8 27.6 13.8 27.6 13.8 27.6 0 0
21 0000000000
22 0 0 13.8 27.6 13.8 27.6 13.8 27.6 0 0
23 0000000000
24 0 0 13.8 27.6 13.8 27.6 13.8 27.6 0 0
25 0000000000
26 13.8 27.6 13.8 27.6 0 0 0 0 13.8 27.6
27 0000000000
28 0 0 5.5 5.5 .5 .5 0 0 0 0
29 (1) 0 0 0 0 4 4 4 4 0 0
30 (2) 0 0 0 0 0 0 6 6 0 0
Terminal
Number
Mode
Selector
OFF
Mode Selector
AUTO
Stand-by
Mode Selector
AUTO
Cranking
Mode Selector
AUTO
Running
Mode Selector
AUTO
Shutdown
Input Voltage
Input
Voltage
Input
Voltage
Input Voltage Input Voltage
13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
31 6666666666
32 6666666666
33 6666666666
34 6666666666
35 6666666666
36 1.4 1.4 13.8 27.6 1.4 1.4 1.4 1.4 1.4 1.4
37 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
38 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
39 (2) 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 0 0
40 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
41 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
42 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
43 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
44 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
45 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
46 1 1 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
47 6666666666
48 6666666666
49 6666666666
50 (3) 0 0 0 0 0 0 6 6 0 0
51 6666666666
52 6666666666
53 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
54 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
55 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
56 (3) 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 0 0
57 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
58 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6 13.8 27.6
Terminal
Number
NOTES
Note 1: AC voltage measured on AC scale of volt-ohmmeter.
Note 2: Low Oil Pressure shut-down circuit. Oil pressure was the cause of shutdown on column 5.
Note 3: Low Oil Pressure pre-alarm circuit. This circuit turned on before the Low Oil Pressure
shutdown occured in column 5.