Multiquip MQP45GM Portable Generator User Manual


 
PAGE 86 — INDUSTRIAL GENERATOR SETS — APPLICATION & INSTALLATION MANUAL — REV. #4 (09/07/07)
APPENDIX — GENERATOR SPECIFICATIONS
TABLE 26. MQ POWER INDUSTRIAL GENERATOR SPECIFICATIONS (cont.)
GENERATOR MQP80GM MQP80IV MQP100GM MQP100IV MQP125IV MQP150IV MQP175IV MQP200IV
Standby Power
Output Rating
75 kW
(93.75 kVA)
75 kW
(93.75 kVA)
100 kW
(125 kVA)
100 kW
(125 kVA)
125kW
(156 kVA)
150 kW
(187.5 kVA)
175 kW
(219 kVA)
200 kW
(250 kVA)
Prime Power
Output Rating
68 kW
(85 kVA)
68 kW
(85 kVA)
90 kW
(112.5 kVA)
90 kW
(112.5 kVA)
113 kW
(141 kVA)
135 kW
(169 kVA)
158 kW
(197.5 kVA)
180 kW
(225 kVA)
Design Synchronous, Revolving Field, Self-Ventilated, Drip-Proof, Single Bearing
Number Of Poles 4-pole Design
Generator RPM 1800
Insulation Class Class H
Excitation System Brushless, Shunt Excitation Design
Armature Connection Wye or Delta
Frequency 60 Hertz
Generator Output Single Phase (1Ø)
Voltage Output
120,127,139, 240, 254, 277
Broad Range Reconnectable
Power Factor 1
Amperage Output -
120/240VAC
313 417 301 333 729 481
Generator Output Three Phase (3Ø)
Voltage Output
208, 220, 240, 416, 440, 480
Broad Range Reconnectable
Power Factor 0.8
Amperage Output -
120/208VAC
260 347 434 520 607 694
Amperage Output -
120/240VAC
226 301 376 451 526 601
Amperage Output -
277/480VAC
113 150 188 226 263 301
Voltage Regulation
(No Load To Full Load)
±1.0%
Environmental Operation
Control Panel Operation
(ICS-30 Control)
0°C ~ +50°C
Control Panel
Storage Temperature
-20°C ~ +70°C
Cooling System Rating 104°F (40°C) With 50/50% Mixture Glycol & Water
CONTINUED ON NEXT PAGECONTINUED FROM PREVIOUS PAGE