Multiquip DCA300SSCU Portable Generator User Manual


 

GENERATOR START-UP PROCEDURE (AUTO MODE)


Before connecting this generator to any
building’s electrical system, a licensed
electrician must install an isolation
  Serious damage to
the building’s electrical system may occur without this
transfer switch.

When connecting the generator to a isolation (transfer)
switch,  have power applied to the generator’s
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.

When running the generator in the  mode,
remember the generator can start up at any time without
warning.  attempt to perform any maintenance
when the generator is in the auto mode.

The engine speed switch must be set to the “High”
position when running in the  mode. Failing
to set the switch in the proper position can result in
damage to your generator when it turns on.
NOTICE
When the generator is set in the  mode, the
generator will automatically start in the event of
commercial power falling below a prescribed level
by means of a contact closure that is generated
automatically by a transfer switch.
NOTICE
When the MPEC control switch is placed in the 
position, the engine glow plugs will be warmed and the
engine will start automatically.
When starting generator in mode use the “Manual
Start-up” procedure except where noted (see below).
1. Perform steps 1 through 5 in the Before Starting section
as outlined in the Manual Starting Procedure.
2. Place the engine speed switch (Figure 51) in the
 position
Figure 51. Engine Speed Switch (High)
3. Place the  (Figure 52) in the
 position.
Figure 52. MPEC Control Switch (AUTO)
4. Continue operating the generator as outlined in the
Manual Start-up procedure (start at step 5).