Multiquip DCA-220SSK Portable Generator User Manual


 
PAGE 54 DCA-220SSK PARTS AND OPERATION MANUAL (STD) REV. #3 (06/05/01)
Figure 62. MPEC Engine Running
Status LED (OFF)
NEVER stop the engine suddenly except
in an emergency. DO NOT use the
emergency stop switch a as method of
shutting down the engine. This switch is
ONLY to be used in the event of an
emergency.
1. To stop the engine in the event of an emergency, PUSH
the emergency stop button ( Figure 63) inward. This button
is located on the generator's engine operating panel,
see page 32, Figure 11.
Emergency Stop
CAUTION
:
Figure 63. Emergency Stop Button
Figure 61. Off/Manual Auto Switch (OFF)
Engine Shutdown
To shutdown the generator use the following procedure:
1. Place both the MAIN, GFCI and LOAD circuit breakers
to the "OFF position".
4. Verify that the "Engine Running" status LED (Figure 62)
on the Microprocessor Engine Control Module (MPEC)
display is "OFF" (not lit).
2. Let the engine cool by running it for 3-5 minutes with no
load applied.
5. Remove the load from the UVW terminal strip (Figure 16).
3. Place the Off/Manual/Auto Switch (Figure 61) in the "OFF/
RESET" position.
DCA-220SSK GENERATOR SHUTDOWN PROCEDURE
Table of Contents