Multiquip DCA-220SSK Portable Generator User Manual


 
DCA-220SSK PARTS AND OPERATION MANUAL (STD) REV. #3 (06/05/01) PAGE 51
10. The generator's frequency meter (Figure 52) displays
the 60 cycle output frequency in HERTZ.
Figure 51. Frequency Meter (Hz)
Figure 52. Voltage Meter (Volts)
11. The generator's voltage meter (Figure 52) displays the
120 VAC in VOLTS. If the voltage is not within the
specified frequency tolerance, use the voltage
adjustment control knob (Figure 53) to increase or
decrease the desired voltage.
A
0
40
60
75
20
Figure 54. Ammeter (No Load)
Figure 53. Voltage Adjust Control
Knob
12. The ammeter (Figure 54) will indicate zero amps with no
load applied. When a load is applied, this meter will
indicate the amount of current that the load is drawing
from the generators alternator.
Figure 49. Off/Manual/Auto Switch (Manual)
8. After engine starts, verify that the "Engine Running"
status LED (Figure 50) on the Microprocessor Engine
Control Module (MPEC) display is "ON" (lit).
Figure 50. MPEC Engine Running Status LED
7. Place the Off/Manual/Auto switch (Figure 49) in the
MANUAL position (down). Observe that the engine begins
to crank.
Figure 51. Engine Ignition Switch
9. If the generator is equipped with a ignition switch, turn
the key to Start position (Figure 51). Once the engine
starts, release the key to the on position.
DCA-220SSK GENERATOR START-UP PROCEDURE (MANUAL)
Table of Contents