DCA-125SSJU SERIES (STANDARD)— PARTS AND OPERATION MANUAL— REV. #4 (06/03/03) — PAGE 49
DCA-125SSJU SERIES — MAINTENANCE
To ensure adequate starting
capability, always have power
applied to the generator's
internal battery charger
.
NOTE
Figure 75. Battery Charger &
Jacket Water Heater Power Connections
Jacket Water Heater and Internal Battery Charger 120
VAC Input Receptacles (OPTIONAL)
This generator is equipped with two 120 VAC, 20 amp input
receptacles located on the output terminal panel.
The purpose of these receptacles is to provide power via
commercial power to the
jacket water heate
r and i
nternal
battery charger
.
These receptacles will ONLY function when commercial
power has been supplied to them (Figure 75). To apply
commercial power to these receptacles, a power cord of
adequate size will be required (See Table 5).
When using the generator in
hot
climates there is no reason
to apply power to jacket water heater. However, if the
generator will be used in
cold
climates it is always a good
idea to apply power to the jacket water heater at all times. To
apply power to the jacket water heater simply apply power to
the jacket water heater receptacle via commercial power
using an power cord of adequate size.
If the generator will be used daily, the battery should normally
not require charging. If the generator will be idle (not used)
for long periods of time, apply power to the battery charger
receptacle via commercial power using an power cord of
adequate size.