PAGE 34 DCA-100SSJU PARTS AND OPERATION MANUAL (STD) REV. #2 (05/03/01)
Circuit Breakers
To protect the generator from an overload, a 3-pole, 250 amp,
main
circuit breaker is provided to protect the UNV output
terminals from overload. In addition two single-pole, 20 amp
GFCI
circuit breakers are provided to protect the GFCI
receptacles from overload. Three 50 amp
load
circuit breakers
have also been provided to protect the load side of the
generator from overload. Make sure to switch
ALL
circuit
breakers to the "OFF" position prior to starting the engine.
OUTPUT TERMINAL FAMILIARIZATION
The Output Terminal Panel is provided with the following:
"
Three 120/240V output receptacles, 50 amp
"
Two 120V input receptacles, 20 amp
"
3 Load Circuit Breakers 250V @50 amps
"
2 Load GFCI Circuit Breakers 120V@ 20amps
Control Box
The Control Box is provided with the following:
"
Main Circuit Breaker 250 amps
"
Over-Current Relay
Output Terminal Panel
The Output Control Panel (See Figure 16) is located on the
right hand side (left from control panel) of the generator.
The UNV lugs are protected by a face plate cover that can
be secured in the close position by a pad lock. (See Figure
13).
120 Volt Receptacle
Two GFCI Duplex Nema 5-20R (120V, 20 Amp) receptacle
is provided on the output terminal. This receptacle can be
used anytime the generator is in operation. The receptacle
is controlled by the circuit breaker located on the control
panel.
Pressing the reset button resets the receptacle after being
tripped. Pressing the "Test Button" (See Figure 14) in the
center of this receptacle will check the GFCI function. The
receptacle should be tested at least once a month.
FIGURE 14. GFCI Test Button
FIGURE 13. Output Terminal Cover
Connecting Load
Loads can be connected to the generator by the UNV Lugs or
the convenience receptacles. (See figure 15). Make sure to
read the operation manual before attempting to connect a load
to the generator.
Maximum Output
The entire load connected to the UNV Lugs, all four slots in the
duplex receptacles, and the must not exceed 88 kW in standby
or 80 kW in prime output.
Twist Lock Dual Voltage Receptacles - To use these
receptacles, place the voltage selector switch in the single
phase 240/120 voltage position and adjust the output
voltage to 240 volts with the voltage regulator on the
Control Panel. Place the voltmeter change-over switch to
the U-W position and the ammeter change-over switch to
the U or W to read the output.
DCA-100SSJU OUTPUT TERMINAL PANEL OVERVIEW
FIGURE 15. Connecting Load