Generac 04390-0, 04456-0, 04390-0 Portable Generator User Manual


 
Generac
®
Power Systems, Inc. 13
Section 3 Operation
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
2.7.3 ADDITIONAL CORROSION
PROTECTION
Periodically spray all engine linkage parts and brack-
ets with corrosion inhibiting spray such as WD-40 or
a comparable product.
2.8 VOLTAGE REGULATOR
ADJUSTMENT
With the frequency between 61-62 Hertz, slowly turn
the slotted potentiometer (Figure 2.5) until line volt-
age reads 244-252 volts.
NOTE:
You must remove the access panel on top of the
control panel to adjust the voltage regulator.
Figure 2.5 – Voltage Adjustment Potentiometer
NOTE:
The voltage regulator is housed above the genera-
tor's control panel. The regulator maintains a volt-
age in direct proportion to frequency at a 2-to-1
ratio. For example, at 62 Hertz, line-to-neutral
voltage will be 124 volts.
3.1 BREAK-IN PROCEDURE
Once the unit has been installed and all electrical
checks have been made, it is strongly recommended
that the following “Break-in Procedure” be completed
to ensure correct generator operation in the future.
1. Set the generator’s Auto/Off/Manual switch to
AUTO.
2. Turn OFF the utility power supply to the transfer
switch using the means provided (such as a utili-
ty main line circuit breaker).
3. The unit will start, and the transfer switch will
transfer to standby.
4. Using the transfer switch’s built-in emergency
load center, turn on circuits to load the generator
to approximately 25% load and run the unit for
one hour.
5. Run the unit for one hour at 50 percent load.
6. Run the unit for one hour at 75 percent load.
7. Run the unit for one hour at 100 percent load.
8. Turn ON the utility power supply to the transfer
switch, which will allow the transfer switch to
transfer back to utility power. The unit will con-
tinue to run for one minute and then shut down.
9. Allow the unit to cool.
10. Drain the oil and remove the oil filter. Replace the
oil filter according to Section 4.4, “Changing the
Oil Filter” (Page 16). Replace the oil with synthet-
ic oil as recommended in Section 4.3, “Changing
the Engine Oil” (Page 15).
11. The generator is now ready for service.
3.2 USING THE AUTO/OFF/MANUAL
SWITCH (FIGURE 3.1)
3.2.1 AUTO POSITION
Selecting this switch position activates fully automatic
system operation. It also allows you to start and exercise
the engine every seven days with the setting of the exer-
cise timer (see Section 3.6, Page 14). This position also
is used for remote starting, when it is set up.
3.2.2 OFF POSITION
This switch position shuts down the engine. This
position also prevents automatic operation.
3.2.3 MANUAL POSITION
Set the switch to MANUAL to crank and start the
engine. Transfer to standby power will not occur
unless there is a utility failure.
Figure 3.1 – Generator Control Panel