Generac 00941-4 Portable Generator User Manual


 
24 Generac
®
Power Systems, Inc.
Section 2 – Installation
IMPACT-36 plus II Recreational Vehicle Generator
2.3.2 COOLING AIR INLET OPENINGS
Provide three air inlet openings, whether the genera-
tor is housed in a conventional compartment or not.
Two of the openings should be 10 square inches and
located as shown in Figure 2.10. The third opening
should provide for a minimum of 40 square inches
unrestricted and be located lower on the compart-
ment door.
NOTE:
Screening, louvers, or expanded metal that cover
air openings restrict air flow that must be com-
pensated for by making the actual air opening pro-
portionately larger. See “Compensating for
Restrictions.”
For conventional compartment mounted units, the
air inlet is generally provided in the compartment
door.
Figure 2.10 — Air Inlet in Compartment Door
IMPORTANT: IF PLANNING TO INSTALL THE GEN-
ERATOR IN A COMPARTMENT, BE SURE TO LEAVE
AT LEAST ONE INCH (2” recommended) OF CLEAR-
ANCE BETWEEN THE GENERATOR AND COM-
PARTMENT WALLS AND CEILING. INCLUDE 26
GAUGE GALVANIZED STEEL LINING AND SOUND
INSULATION WHEN MEASURING FOR THIS 1 INCH
(2” recommended) CLEARANCE.
When the unit is installed on a suspended mounting
system, one of several different methods of supplying
air flow may be used as follows:
Provide a door in the vehicle skirt having an air
inlet opening (Figure 2.11).
Figure 2.11 — Suspended Mount Inlet Door
Using ductwork (Figure 2.12). The installer must
be sure air is available to the top of the generator
since air inlets are located at the top.
Figure 2.12 — Air Inlet Using Ductwork
By providing an opening in the vehicle skirt and
space above the generator for cooling air flow
(Figure 2.13). Recommended clearance above the
top of the generator is at least 2 inches.
Figure 2.13 — Air Inlet in Vehicle Skirt
10 Square Inches
(Optional Openings)
40 Square Inches
(Minimum Opening)