Baldor TS25 Portable Generator User Manual


 
4-18 Operation
MN2417
Table 4-9 Setpoints Continued
GCB CloseDelay
GCB can be closed earliest GCB CloseDelay after Stabil time when all
electric values are in overunder voltage and overunder frequency limits.
Step: 1 s; Range: 0 300 s
Stabil time Generator Nominal voltage is detected during genset start after starter is
switched off and Idle time elapses. Electric generator protections are
active since detection. Step: 1 s; Range: 0 300 s
MinStpValvTime Binary output Stop solenoid closes when stop sequence begins and
closes at least for MinStpValvTime. Example MinStpValvTime = 20 sec.
a) When engine stops (RPM=0) in 10 seconds, Binary output Stop
solenoid still stays closed for 10 sec.
b) When engine stops in 30 seconds, Binary output Stop solenoid opens
10 seconds after RPM=0 and Vg =0 and Oil pressure = 0. Those 10 sec is
fix time for safe stop. Step: 1s; Range: 0 180 s
Note: Stop of engine is detected when all following conditions are met:
RPM =0, Oil pressure < StartingPOil and Generator voltage < 10 VAC.
Stop fail is detected when is difference between those conditions, e.g
RPM=O and Generator voltage > 10V.
Cooling time Runtime of the unloaded genset to cool the engine before stop.
Step: 1s; Range: 0 3600 s
D+ function ENABLED: The D+ terminal is used for both functions running
engine
detection and charge fail detection.
CHRGFAIL: The D+ terminal is used for charge fail detection only
DISABLED: The D+ terminal is not used.
Note: Magnetization current is independent of this setpoint value.
Eng prot del During the start of the genset, some engine protections have to be
blocked (e.g. Oil pressure). The protections are unblocked after the
Protection del time. The time starts after reaching Start RPM.
Step: 1s; Range: 0 300 s
Horn timeout Max time limit of horn sounding. Set to zero if you want to leave the output
HORN open. Step: 1s; Range: 0 600 s
Overspeed Threshold for over speed protection.
Step: 1% of nominal RPM; Range: 100 150%
Wrn Oil press Warning threshold level for ANALOG INPUT 1.
Step: 1 psi; Range: Sd Oil press 10000
Sd Oil press Shutdown threshold level for ANALOG INPUT 1.
Step: 1 psi; Range: 100 Wrn Oil press
Oil press del Delay for ANALOG INPUT 1. Step: 1 s; Range: 0 180
Sd Water temp Warning threshold level for ANALOG INPUT 2.
Step: 1 °C; Range: Wrn Wtemp 10000
Wrn Water temp Warning threshold level for ANALOG INPUT 2.
Step: 1 °F; Range: Wrn Wtemp low Sd Water temp
Wrn Wtemp low Warning threshold level for low value on ANALOG INPUT 2.
Step: 1 °F; Range: 100 Wrn Water temp
Water temp del Delay for ANALOG INPUT 2 alarm. Step: 1 s; Range: 0 180 s
Wrn Fuel Level Warning threshold level for ANALOG INPUT 3.
Step: 1 %; Range: Sd Fuel Level 10000
Sd Fuel Level Shutdown threshold level for ANALOG INPUT 3.
Step: 1 %; Range: 100 Wrn Fuel Level
Fuel Level del Delay for ANALOG INPUT 3. Step: 1 s; Range: 0 180 s
Batt overvolt Warning threshold for high battery voltage.
Step: 0,1 V; Range: Batt undervolt 40V
Batt undervolt Warning threshold for low battery voltage.
Step: 0,1 V; Range: 8V Batt overvolt
Batt volt del Delay for low battery voltage alarm. Step: 1s; Range: 0 600 s
NextServTime Counts down when engine running. If reaches zero, an alarm appears.
Step: 1h; Range: 0 65535h