Baldor TS25 Portable Generator User Manual


 
Operation 4-15
MN2417
Table 4-7 Binary outputs Continued
Common Wrn
Output closes when any warning alarm appears.
The output opens, if alarm is not active and FAULT RESET is pressed.
Common Sd Output closes when any shutdown alarm appears.
The output opens, if alarm is not active and FAULT RESET is pressed.
Sd OilPress Output closes if the oil pressure shutdown alarm activates.
The output opens, if alarm is not active and FAULT RESET is pressed.
Wrn OilPress Output closes if the oil pressure warning alarm activates.
The output opens, if alarm is not active and FAULT RESET is pressed.
Sd Water Temp Output closes if the water temperature shutdown alarm activates.
The output opens, if alarm is not active and FAULT RESET is pressed.
Wrn Water Temp Output closes if the water temperature warning alarm activates.
The output opens, if alarm is not active and FAULT RESET is pressed.
OFF mode The output is closed, if OFF mode is selected.
MAN mode The output is closed, if MAN mode is selected.
AUT mode The output is closed, if AUT mode is selected.
Sd FuelLevel The output closes if the Fuel level shutdown alarm activates.
Wrn FuelLevel The output closes if the Fuel level warning alarm activates.
WrnTempLow The output closes if the low water temperature warning alarm
activates.
Not In Auto The output closes in OFF and MAN mode.
Vgen warning The output closes if the generator over/under voltage warning alarm
activates.
fgen warning Output closes if the generator over/under frequency warning alarm
activates.
Overload wrn Output closes if the generator overload warning alarm activates.
Running Output closes if the engine is in Running state.
ServiceTime Output closes if the ServiceTime alarm activates.
The output opens, if alarm is not active and FAULT RESET is pressed.
BI1 ... BI6 stat
IOM BI1 ... IOM BI8 stat
The outputs give information about the assigned binary input.
In case the assigned binary input is configured to alarm type, then the
output closes when the alarm activates.
The output opens, if alarm is not active and FAULT RESET is pressed.
In case the assigned binary input is configured to any control function,
the output propagates the state of the input.
AnImIOM 1..4 Sd Output closes if shutdown alarm on the appropriate IOM or PTM
analog input activates.
The output opens, if alarm is not active and FAULT RESET is pressed.
ECU CommOK Output is closed when ECU communication is OK.
VP warning Output is closed when at least on of following alarms is active:
Overspeed Alarm, Oil Pressure Alarm, Oil Temperature Alarm,
Coolant Temperature Alarm, Coolant Level Alarm, Charge Alarm
Supplying load Closed when the generator current is > 0,5% of the CT ratio.
Exact formulas: Output is closed when the current at least in one
phase is for 1 sec over CT ratio/200+2
Output is opened when the current in all three phases is for 1 sec
below CT ratio/200+2
Note: Values are truncated after division, not rounded