4-16 Operation
MN2417
Analog Inputs Three analog inputs for resistive sensor 0 to 2400 Ù measuring are available on IL controller.
Use LiteEdit software to modify configuration.
The Analog inputs values assignment (AI1 = Oil press, AI2 = Water temp, AI3 = Fuel level) is fix.
It is possible to configure on each Analog input:
S Reading from IL Analog inputs or from Engine Control Unit via CAN bus (J1939)
S Sensor characteristics from the list,
S Value dimension (e.g. psi − bars, °F − °C, % − l)
S Number of decimal points (0, 1, 2, ...).
Note: Corresponding Analog input terminal is dead when reading is switched to ECU.
All values from ECU shall show ####, but no alarm is displayed when CAN communication
is interrupted.
Warning and shut−down limits are adjusted in Engine protection group.
Table 4-8 Analog Inputs
AI1 Oil press Oil pressure analog input. Default VDO sensor in range 0 to 145 psi.
AI2 Water temp
Water temperature analog input. Default VDO sensor in range 32 to 212°F
AI3 Fuel level Fuel level analog input. Default VDO sensor 0−180R = 0−100%.
Set points
Table 4-9 Setpoints
EnterPassword Password is a four−digit number. Password enables change of relevant
protected set points Use ⇑or ⇓keys to set and ENTER key to enter the
password.
ChangePassword Use ⇑or ⇓keys to set and ENTER key to change the password.
Gen−set name User defined name, used for InteliLite identification at remote phone or
mobile connection. Gen−set name is max 14 characters long and have to
be entered using LiteEdit software.
Nomin power(3ph) Nominal power of the generator in three phases connection.
Step: 1 kW; Range: 1 − 3000 kW
Nomin power(1ph) Nominal power of the generator in single−phase connection.
Step: 1 kW; Range: 1 − 3000 kW
CT Ratio Gen−set phases current transformers ratio.
Step: 1 A; Range: 1 − 5000 A / 5A
PT ratio Gen−set potential transformers ratio.
Step: 0,1 V / V; Range: 0,1 − 500,0 V / V
Nominal freq Nominal generator frequency (usually 50 or 60 Hz )
Step: 1Hz; Range: 45 − 65 Hz
Gear teeth Number of teeth on the engine gear for the pick−up. Set to zero, if no
pick−up is used. Engine speed is counted from the generator frequency.
Step: 1; Range: 0 − 500
Note: Generator frequency can be used only when generator voltage
(min 5V) is present before reaching of the firing speed
(Starting RPM) after start.
Nominal RPM Nominal engine speed. Step: 1RPM; Range: 100 − 4000 RPM.
Mode IL [ OFF, MAN, AUT ]
Equivalent to Controller mode changes by MODE" or MODEA buttons.
Note: Controller Mode change can be separately password protected.
RS232 mode
[Standard/Modbus ]
Communication protocol switch.
Standard: LiteEdit communication protocol. Modbus: Modbus protocol.
Note: For detail description see chapter Modbus protocol.
Num rings AA Number of rings prior to open modem connection. Step: 1; Range: 1 − 30
Note: NumberRings AA change is not activated immediately. It is activated
after controller is switched on or when modem is connected to controller.