6. INSTALLATION CHECKLIST BATTERY INSTALLATION
 Battery is connected properly.
 Recommended battery is installed.
 Cables are clean and tight.
 Terminals are coated with anti-corrosion grease, and
terminal covers are positioned.
FUEL SYSTEM
 Complies with local and NFPA codes.
 Fuel is connected and checked for leaks.
 Correct fuel pressure (11-14 inches of water (0.6 psi) at
all load ranges).
 Load block adjusted for maximum power for natural gas
fuel.
LOCATION
 Unit is fastened to the appropriate mounting pad.
 Louvers are free from obstruction.
 Exhaust is clear of flammable objects and debris.
ELECTRICAL CONNECTIONS
 Complies with local code requirements and all National
Electrical Codes.
 Utility is connected and present.
 Transfer switch is connected.
 All wires running outside of the generator are in NEC-
approved conduit. *Note: Utility wires and transfer switch
control wires must be in separate conduit.
 Unit is grounded to an approved earth ground.
COOLING AND VENTILATING
 All inlets and outlets are free from obstruction.
OTHER
 Verify that the unit is filled to the proper level with the
proper break-in oil. Adjust as required.