Chapter 5. Accessing the Controller via a Network Management System (NMS) 161
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
The status of communication with the Power System.
(1) unknown
(2) normal
(3) interrupt indicates some errors occurred between Power System
and agent
The status of battery modes.
(1) unknown
(2) FloatCharging
(3) ShortTest
(4) EqualizeChargingForTest
(5) ManualTesting
(6) PlanTesting
(7) ACFailTesting
(8) ACFail
(9) ManualEqualizeCharging
(10) AutoEqualizeCharging
(11) CyclicEqualizeCharging
(12) MasterEqualizeCharging
(13) MasterBatteryTesting
The number of SM AC module.
The number of SM BAT module.
The number of SM IO module.
Controller Alarm Trap Group
The sequence number of last submitted alarm trap.
alarmTrapTable
(alarmTrapEntry)
Table holding information about the submitted alarm traps.
alarmTrapEntry is the entry (conceptual row) in the alarmTrapTable.
The unique sequence number of this alarm trap.
Date and time when event occurred (local time), including timezone if
supported by Controller.
The type of alarm change. One of...
(1) activated
(2) deactivated
The severity of the alarm. One of...
(1) warning - OA, lowest level of alarm severity
(2) minor - A3
(3) major - MA
(4) critical - CA, highest level of alarm severity
Free-text description of alarm.