UM1M820BNA User Instructions
Issue AH, March 4, 2013 Spec No. 1M820BNA (Model M820B)
Spec No. 1M820DNA (Model M820D)
160 Chapter 5. Accessing the Controller via a Network Management System (NMS)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
The name of the equipment manufacturer.
The manufacturers model designation of the power system.
identControllerFirmwareVersion
The firmware (software) version of the Controller.
The name of the power plant. This object should be set by the
administrator.
Controller System Value Group
Status of the complete plant (highest alarm). One of...
(1) unknown - status has not yet been defined
(2) normal - there are no activated alarms
(3) warning - OA, lowest level of 'abnormal' status
(4) minor - A3
(5) major - MA
(6) critical - CA, highest level of 'abnormal' status
(7) unmanaged
(8) restricted
(9) testing
(10) disabled
System voltage, stored as mV.
System current, stored as mA.
Used capacity, stored as percentage of the total capacity .
Power System Battery Group
Battery voltage, stored as mV.
Battery current, stored as mA.
The AC line A voltage, stored as mV.
The AC line B voltage, stored as mV.
The AC line C voltage, stored as mV.
Power System Temperature Group
The first route temperature, stored as 0.001 Celsius degree.
The second route temperature, stored as 0.001 Celsius degree.