Viking Sprinkler 11a Sprinkler User Manual


 
TECHNICAL DATA
March 7, 2008
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
MICROMATIC
®
AND
MicromaticHP
®
STANDARD
RESPONSE PENDENT
SPRINKLERS
Approval Chart 3
MicromaticHP
®
Standard Response Pendent Sprinklers
Maximum 250 PSI (17 bar) WWP
Sprinkler
Base Part
Number
1
SIN
Thread Size
Nominal
K-Factor
Overall
Length
Listings and Approvals
3
(Refer also to Design Criteria on page 11g.)
NPT BSP U.S. metric
2
Inches mm cULus
4
FM NYC VdS LPCB
Standard Orifice
09992 VK122 1/2” 15 mm 5.6 80.6 2-1/4” 58 A1, D2 -- -- -- -- -- --
Small Orifice
7
09994
7,8
VK023 1/2” 15 mm 2.8 40.3 2-1/4” 58 A1 -- -- -- -- -- --
Installed with the Viking Micromatic
®
Model E-1 or E-2 Recessed Escutcheon
09992 VK122 1/2” 15 mm 5.6 80.6 2-1/4” 58 C1 -- -- -- --
--
--
09994
7,8
VK023 1/2” 15 mm 2.8 40.3 2-1/4” 58 C1 -- -- -- -- -- --
Installed with the Viking Microfast
®
Model F-1 Adjustable Escutcheon
09992 VK122 1/2” 15 mm 5.6 80.6 2-1/4” 58 B1 -- -- -- --
--
--
09994
7,8
VK023 1/2” 15 mm 2.8 40.3 2-1/4” 58 B1 -- -- -- -- -- --
Approved Temperature Ratings
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F
(141 °C), and 360 °F (182 °C)
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F
(141 °C)
C - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
D - 500 °F (260 °C)
8
Approved Finishes
1 - Brass, Chrome-Enloy
®
, White Polyester
5,6
, Black Polyester
5,6
, and
Black Teflon
®5
2 - Brass and Chrome-Enloy
®
Footnotes
1
Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2
Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3
This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4
Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
5
cULus Listed as corrosion resistant.
6
Other colors are available on request with the same Listings and Approvals as the standard colors.
7
Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated
wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or
internally galvanized.
8
The sprinkler orifice is bushed.
9
Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above
300 °F (149 °C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F (149 °C),
the response time of the Ultra-High temperature rated sprinkler may be severely retarded.