Viking Sprinkler 11a Sprinkler User Manual


 
MICROMATIC
®
AND
MicromaticHP
®
STANDARD
RESPONSE PENDENT
SPRINKLERS
TECHNICAL DATA
March 7, 2008
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
Approval Chart 2
Micromatic
®
Standard Response Pendent Sprinklers
Maximum 175 PSI (12 bar) WWP
Sprinkler
Base Part
Number
1
SIN
Thread Size
Nominal
K-Factor
Overall
Length
Listings and Approvals
3
(Refer also to Design Criteria on page 11g.)
NPT BSP U.S. metric
2
Inches mm cULus
4
FM NYC
7
VdS LPCB
12
Installed with the Viking Micromatic
®
Model E-1 or E-2 Recessed Escutcheon
10139 VK102 1/2” 15 mm 5.6 80.6 2-3/16” 56 B1 A2
10
B1 B2 B2 C2 --
10173
11
VK102 -- 15 mm 5.6 80.6 2-3/16” 56 B1 A3
10
-- -- B2 -- --
10223 VK202 1/2” 15 mm
8.0 115.2 2-3/8” 60 B1 B3
10
B1 -- -- -- --
10142 VK202 3/4” 20 mm
8.0 115.2 2-5/16” 59 B1 B3
10
B1 -- B2 C2 --
10170 VK202 -- 20 mm
8.0 115.2 2-3/8” 60 B1 B3
10
-- -- B2 C2 --
12105 VK202 3/4” 20 mm
8.0 115.2 2-3/16” 56 -- -- -- B2 -- B2 --
10221
8,9
VK003 1/2” 15 mm 2.8 40.3 2-3/16” 56 B1 A3
8
B1 -- -- -- --
10222
8,9
VK004 1/2” 15 mm
4.2 60.5
2-1/4” 58 B1 -- B1 -- B2 -- --
Installed with the Viking Microfast
®
Model F-1 Adjustable Escutcheon
10139 VK102 1/2” 15 mm 5.6 80.6 2-3/16” 56 B1 -- B1 D2 B2
--
--
10223 VK202 1/2” 15 mm
8.0 115.2 2-3/8” 60 B1 -- B1 B2 -- -- --
10221
8,9
VK003 1/2” 15 mm 2.8 40.3 2-3/16” 56 B1 -- B1 -- --
--
--
Approved Temperature Ratings
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 212 °F
(100 °C)
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
C - 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
D - 286 °F (141 °C)
Approved Finishes
1 - Brass, Chrome-Enloy
®
, White Polyester
5,6
, Black Polyester
5,6
, and
Black Teflon
®5
2 - Brass, Chrome-Enloy
®
, White Polyester
6
, and Black Polyester
6
3 - Brass and Chrome-Enloy
®
Footnotes
1
Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3
This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4
Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
5
cULus Listed as corrosion resistant.
6
Other colors are available on request with the same Listings and Approvals as the standard colors.
7
Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 12.
8
Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated
wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or
internally galvanized.
9
The sprinkler orifice is bushed.
10
FM Approval of Viking Micromatic
®
Standard Response Recessed Pendent Sprinklers installed with the Viking Micromatic
®
Model E-1 or E-2 Recessed
Escutcheon is limited to wet systems and preaction systems qualifying as wet systems, for hazard occupancies up to and including Ordinary Hazard,
Group II.
11
Sprinkler 10173 is available on special order.
12
Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40181, 0832-CPD-2001, and 0832-CPD-2003.
Sprinkler 11e