Viking Sprinkler 11a Sprinkler User Manual


 
TECHNICAL DATA
March 7, 2008
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
MICROMATIC
®
AND
MicromaticHP
®
STANDARD
RESPONSE PENDENT
SPRINKLERS
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Screw: Brass UNS-C36000
Pip Cap for Sprinklers 09992, 09994, and 10221: Brass UNS-C31400 or UNS-C31600
Pip Cap and Insert Assembly for all other Sprinklers: Copper UNS-C11000 and Stainless Steel UNS-S30400
Pip Cap Attachment: Brass UNS-C36000
Ejector Spring (for Sprinkler 12105): Stainless Steel
For Teflon
®
Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon
®
Coated
For Polyester Coated Sprinklers: Belleville Spring-Exposed
Ordering Information: (Also refer to the current Viking price list.)
Order Micromatic
®
and MicromaticHP
®
Standard Response Pendent Sprinklers by first adding the appropriate suffix for the sprin-
kler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome-Enloy
®
= F, White Polyester = M-/W, Black Polyester = M-/B, Black Teflon
®
= N, Wax Coated = C,
Wax Over Polyester = V-/W
Temperature Suffix (°F/°C): 135°/57° = A, 155°/68° = B, 175°/79° = D, 200°/93° = E, 212°/100° = M, 286°/141° = G, 360°/182° = H,
500°/260° = L, OPEN = Z (Teflon
®
only).
For example, sprinkler VK102 with a 1/2” thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 10139AB
Available Finishes And Temperature Ratings:
Refer to Table 1
Accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 10896W/B (available since 2000).
B. Wrench for recessed sprinklers: Part No. 12144W/B** (available since 2003)
C. Wrench for wax coated sprinklers: Part No. 13577W/B** (available since 2006)
NOTE: RECESSED PENDENT SPRINKLERS WITH PROTECTIVE CAPS MUST USE WRENCH 12144W/B.
**A ½” ratchet is required (not available from Viking).
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands,
causing the glass to shatter, releasing the pip cap and sealing spring
assembly. Water flowing through the sprinkler orifice strikes the sprinkler
deflector, forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Micromatic
®
and MicromaticHP
®
Standard Response Pendent
Sprinklers are available through a network of domestic and international
distributors. See The Viking Corporation web site for the closest distributor
or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact
Viking directly.