Viking Sprinkler 11a Sprinkler User Manual


 
MICROMATIC
®
AND
MicromaticHP
®
STANDARD
RESPONSE PENDENT
SPRINKLERS
TECHNICAL DATA
March 7, 2008
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
Viking Micromatic
®
and MicromaticHP
®
Standard Response Pendent Sprinklers are
small, thermosensitive, glass-bulb spray sprinklers available in several different fin-
ishes, temperature ratings, and K-Factors to meet design requirements. The special
Polyester and Teflon
®
coatings can be used in decorative applications where colors are
desired. In addition, these coatings have been investigated for installation in corrosive
atmospheres and are cULus listed as corrosion resistant as indicated in the Approval
Chart. (Note: FM Global has no approval classification for Teflon
®
and Polyester coat-
ings as corrosion resistant.)
Viking standard response sprinklers may be ordered and/or used as open sprinklers
(glass bulb and pip cap assembly removed) on deluge systems. Refer to Ordering
Instructions on page 11b.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Classes 2001, 2002, 2006, 2015, and 2017
NYC Approved: MEA 89-92-E, Volume 12
ABS Certified: Certificate 04-HS407984A-PDA
VdS Approved: Certificate G4040096, G4040098, G4060058, G4060059, G4980001, G4980002, G4980005, and G4980007
LPC Approved: Ref. No. 096e/06 and 167a/04
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40141, 0786-CPD-40181, 0832-CPD-2001, and
0832-CPD-2003
MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008, and RINA Certificate
No. MED497705C5
NOTE: Other International approval certificates are available upon request.
Refer to the Approval Charts on pages 11d-f and Design Criteria on page 11f for cULus and FM approval requirements that must
be followed.
3. TECHNICAL DATA
Speci cations:
Available since 1997.
Minimum Operating Pressure: Refer to the Approval Chart
Maximum Working Pressure: Sprinklers VK023 and VK122 are rated for
use with water working pressures ranging from the minimum 7 psi
(0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres-
sure (HP) sprinklers can be identified by locating “250” stamped on
the deflector. All other Part Nos. not mentioned above are rated to a
maximum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A. Patent No. 4,831,870
Thread size: Refer to the Approval Charts
Nominal K-Factor: Refer to the Approval Charts
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: Refer to the Approval Charts
Material Standards:
Frame Casting: Brass UNS-C84400
Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500 for Sprinklers 10139, 10142, 10170, 10173, 10223, and
12105. Brass UNS-C26000 for all other Sprinklers.
Bushing (for Sprinklers 09994, 10189, 10221, and 10222): Brass UNS-C36000
Bulb: Glass, nominal 5 mm diameter
Form No. F_100397 Replaces page 11a-h, dated October 12, 2007.
(Added Dry System note in approval chart for Small Orifice)
Viking Technical Data may be found on
The Viking Corporation’s Web site at
http://www.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.