Shindaiwa DG250MI Portable Generator User Manual


 
- 31 -
And then adjust the speed by speed control knob and adjust to the No-load revolution.
No-load revolution
50 Hz Operation 1575 min
-1
(52.5 Hz)
60 Hz Operation 1890 min
-1
(63.0 Hz)
<Caution>
By adjusting the speed to the above revolutions, the frequency will be 50Hz or 60Hz.
Lock the Speed Control handle with locknut
<Caution>
Ensure that the speed control handle is surely locked with locknut, otherwise the
frequency (engine revolution) may fluctuate.
Adjust to the required voltage by adjusting Voltage regulator.
Turn the circuit breaker to ON position to send power to the load side.
!
Danger
: Electrical Shock Injuries
Before turning the circuit breaker to ON position to send power to the load side, always ensure
that any circuit breaker and switch of loads are positioned to OFF.
In the case the generator and the load are away from each other, proceed with the above
steps, communicating well with the other person by the load in order to prevent from
accident.
9.2 During Operation
9.2.1 Post startup check
Make sure that all meters (gauges) and displays are working properly (refer to 5. Equipment)
Check for any unusual vibration or noise
Check for any unusual color from the exhaust. Under normal condition, the exhaust fume has no
color or light bluish color.
<Caution>
If finding out abnormality, consult with the distributor or our engineering section in order to repair,
without using the machine.