50 Cheetah 10K.7 SCSI Product Manual, Rev. D
8.2 Drive orientation
The balanced rotary arm actuator design of the drive allows it to be mounted in any orientation. All drive perfor-
mance characterization, however, has been done with the drive in horizontal (discs level) and vertical (drive on
its side) orientations, and these are the two preferred mounting orientations.
8.3 Cooling
The host enclosure must dissipate heat from the drive. You should confirm that the host enclosure is designed
to ensure that the drive operates within the temperature measurement guidelines described in Section 6.4.1. In
some cases, forced airflow may be required to keep temperatures at or below the temperatures specified in
Section 6.4.1.
If forced air is necessary, possible air-flow patterns are shown in Figure 21. The air-flow patterns are created
by fans either forcing or drawing air as shown in the illustrations. Conduction, convection, or other forced air-
flow patterns are acceptable as long as the temperature measurement guidelines of Section 6.4.1 are met.
Figure 21. Air flow (suggested)
Above unit
Under unit
Note. Air flows in the direction shown (back to front)
or in reverse direction (front to back)
Above unit
Under unit
Note. Air flows in the direction shown or
in reverse direction (side to side)