Roberts Gorden CTCU 15 Patio Heater User Manual


 
WARNING
Attach this information to the wall near the ROBERTS GORDON
®
heater
Read the Installation, Commissioning, Operation and Service Manual thoroughly before installation, operation or service.
OPERATING INSTRUCTIONS
1. STOP! Read all safety instructions on this information sheet.
2. Open the manual gas valve in the heater supply line.
3. Turn on electric power to the heater.
4. Set the thermostat to desired setting (above ambient temperature).
The automatic starting sequence begins.
NOTE: Following long shutdown periods, the burner control may go to
to 'LOCKOUT' during the start sequence. Push the reset button to
recommence firing. Contact service department if 'LOCKOUT'
continues (see manual for details).
1. Turn the thermostat/time switch to 'OFF'. The burner will turn 'OFF'
immediately, but fans will continue to cool heat exchanger until the fan
thermostat switches off.
1. Set the thermostat to off or the lowest setting.
2. Turn off electric power to the heater.
3. Turn off the manual gas valve in the heater supply line.
4. Call your registered installer/contractor qualified in the installation
and service of gas-fired heating equipment.
IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,
FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER
Fire Hazard
Some objects can catch fire or explode when placed
close to heater.
Keep all flammable objects, liquids and vapors the
required clearances to combustibles away from heater.
Failure to follow these instructions can result in death,
injury or property damage.
TO TURN OFF THE HEATER
®
50 cm**
10 cm
30 cm
15 cm
Clearances to Combustibles
Wall
Terminal
Roof Terminal
Air
Intake
Flue
15 cm
2.5 - 3.5 m*
3 m
25 cm
Installation Clearances
3 m
Roof Terminal
**80 cm is necessary to service heater
*Heaters may be mounted at a higher level if
destratification fans are installed.
© 2007 Roberts-Gordon, LLC www.rg-inc.com Printed in U.S.A P/N 91040029 Rev B
Fax: +44(0)121 506 7701
Service Telephone: +44(0)121 506 7709
Service Fax: +44(0)121 506 7702
E-mail: uksales@rg-inc.com
E-mail: export@rg-inc.com
Roberts-Gordon, LLC
1250 William Street
P.O. Box 44
Buffalo, NY 14240-0044 USA
Roberts-Gordon Europe Limited
Unit A, Kings Hill Business Park
Darlaston Road, Wednesbury
West Midlands WS10 7SH UK
Telephone: +44(0)121 506 7700
Installation Code and Annual Inspections:
All installations and service of ROBERTS GORDON
®
equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and
conform to all requirements set forth in the ROBERTS GORDON
®
manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help
facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON
®
equipment and perform service where necessary,
using only replacement parts sold and supplied by Roberts-Gordon.
For installations at elevations above 2000' (610 m), the appliance shall be derated 4% for each 1000' (305 m) of elevation above sea level.
Further Information:Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON
®
representatives.
Please contact us for any further information you may require, including the Installation, Commissioning, Operation and Service Manual.
These products are not for residential use.
Telephone: 716.852.4400
Fax: 716.852.0854
Toll Free: 800.828.7450