Roberts Gorden CTCU 15 Patio Heater User Manual


 
COMBAT
®
CTCU UNIT HEATERS INSTALLATION OPERATION AND SERVICE MANUAL
34 of 42
15.3 Troubleshooting for Flame Supervision System
15.4 Troubleshooting for Solenoid Valves
NOTE: Minimum flame probe current 1 µA DC.
To measure flame current, connect a 0 - 50 µA DC meter in
series with the flame probe. If the meter reads negative
values, then reverse the test leads.