Multiquip DCA-70SSJU Portable Generator User Manual


 
PAGE 28 — DCA-70SSJU SERIES — OPERATION AND PARTS MANUAL (STD) — REV. #5 (06/03/03)
Output Terminal Familiarization
The “
Output Terminal Panel
” (Figure 8) is provided with
the following:
Three (3) 240V output receptacles, 50 amp
Three (3) Circuit Breakers 240V @50 amps
Two (2) 120V GFCI receptacles, 20 amp
Two (2) GFCI Circuit Breakers 120V@ 20 amps
One Main Circuit Breaker 250V @175 amps
Five (5) Output Terminal Lugs
Output Terminal Panel
The
Output Terminal Panel
(Figure 8) shown below is located
on the right-hand side (left from control panel) of the generator.
Lift up on the cover to gain access to receptacles and terminal
lugs.
NOTE
Terminal legs “O” and “Ground
are considered
bonded grounds
.
Figure 8. Output Terminal Panel
DCA-70SSJU SERIES — OUTPUT TERMINAL PANEL FAMILIARIZATION