PAGE 50 — DCA-40SSAI — PARTS AND OPERATION MANUAL — FINAL COPY (07/09/01)
1. To stop the engine in the event of an emergency, switch
the MAIN, GFCI and LOAD circuit breakers to ‘OFF’
position.
2. Turn the starter switch key to ‘Stop’ position.
EMERGENCY STOP
ENGINE SHUTDOWN
To shutdown the generator, use the following procedure:
1. Switch both the MAIN, GFCI and LOAD circuit breakers
(Figure 52) to the “OFF” position.
2. Turn and push the engine throttle control lever (Figure
53) to the idle (low) position.
3. Let the engine cool by running it for 3-5 minutes with no
load applied.
4. Turn the starter switch key to ‘Stop” position (Figure
54).
5. Remove the load from the UNV terminal strip.
Figure 52. Main, GFCI and Load
circuit breakers
Figure 53. Engine Throttle Control Lever
DCA-40SSAI — GENERATOR SHUTDOWN PROCEDURE
Figure 54. Off/Manual Auto Switch