DCA-40SSAI PARTS AND OPERATION MANUAL FINAL COPY (07/09/01) PAGE 49
A
0
40
60
75
20
Figure 46. Ammeter (No Load)
11. The ammeter (Figure 46) will indicate zero amps with no
load applied. When a load is applied, this meter will
indicate the amount of current that the load is drawing
from the generators alternator.
Figure 49. Engine Tachometer
DCA-40SSAI GENERATOR START-UP PROCEDURE
12. The engine oil pressure gauge (Figure 47) will indicate
the oil pressure (kg/ cm
2
)
of the engine. Under normal
operating conditions the oil pressure is approximately
25 psi.
13. The coolant temperature gauge (Figure 48) will indicate
the coolant temperature. Under normal operating
conditions the coolant temperature is between 165 and
215 degrees Fahrenheit.
WATER
TEMP
Figure 48. Coolant Temperature Gauge
Figure 47. Oil Pressure Gauge
14. The tachometer (Figure 49) will indicate the speed of
the engine when the generator is operating. Under normal
operating conditions this speed is approximately 1800
RPMs.
16. Observe the generator's ammeter (Figure 51) and verify
it reads the anticipated amount of current with respect
to the load. The ammeter will only display a current
reading if the load is in use.
17. The generator will run until manually stopped or an
abnormal condition occurs.
Figure 50. Main and GFCI Circuit Breakers
Figure 51. Ammeter (Load)
A
0
40
60
75
20
15. Turn the MAIN, GFCI and LOAD circuit breakers to
their ON position (Figure 50).