Multiquip DCA-220SSJ Portable Generator User Manual


 
PAGE 18 — DCA-220SSJ— OPERATION AND PARTS MANUAL — REV. #1 (03/22/07)
DCA-220SSJ — GENERAL INFORMATION
DCA-220SSJ Whisperwatt™ Series Familiarization
Generator
The MQ Power Model DCA-220SSJ is a 176 kW
generator
(Figure 5) that is designed as a high quality portable (requires
a trailer for transport) power source for telecom sites, lighting
facilities, power tools, submersible pumps and other industrial
and construction machinery.
Engine Operating Panel
The “Engine Operating Panel” is provided with the following:
Tachometer
Water Temperature Gauge
Oil Pressure Gauge
Charging Ammeter Gauge
Fuel Level Gauge
Engine Speed Switch
Panel Light/Panel Light Switch
Auto ON/OFF Engine Controller (MPEC)
Preheat Lamp
Warning Lamp
Emergency Stop Lamp
Emergency Stop Button
Open Delta Excitation System
The DCA-220SSJ generator is equipped with the state of
the art "
Open-Delta
" excitation system. The open delta
system consist of an electrically independent winding wound
among stationary windings of the AC output section.
There are four connections of the open delta A, B, C and D.
During steady state loads, the power from the voltage regulator
is supplied from the parallel connections of A to B, A to D,
and C to D. These three phases of the voltage input to the
voltage regulator are then rectified and are the excitation
current for the exciter section.
When a heavy load, such as a motor starting or a short
circuit occurs, the automatic voltage regulator (AVR)
switches the configuration of the open delta to the series
connection of B to C. This has the effect of adding the voltages
of each phase to provide higher excitation to the exciter
section and thus better voltage response during the
application of heavy loads.
The connections of the AVR to the AC output windings are
for sensing only. No power is required from these windings.
The open-delta design provides virtually unlimited excitation
current, offering maximum motor starting capabilities. The
excitation does not have a "
fixed ceiling
" and responds
according the demands of the required load.
Engine
The DCA-220SSJ is powered by a 6 cylinder, water cooled,
direct injection, turbocharged
John Deere 6068HF485 Turbo
Diesel Engine
. This engine is designed to meet every
performance requirement for the generator. Reference Table 1
for engine specifications.
In keeping with MQ Power's policy of constantly improving
its products, the specifications quoted herein are subject to
change without prior notice.
Electric Governor System
The electric governor system controls the RPMs of the en-
gine. When the engine demand increases or decreases, the
governor system regulates the frequency variation to ±.25%.
Extension Cables
When electric power is to be provided to various tools or
loads at some distance from the generator, extension cords
are normally used. Cables should be sized to allow for
distance in length and amperage so that the voltage drop
between the generator and point of use (load) is held to a
minimum. Use the cable selection chart (Table 6) as a guide
for selecting proper extension cable size.
Generator Control Panel
The “Generator Control Panel” is provided with the following:
Frequency Meter (Hz)
AC Ammeter (Amps)
AC Voltmeter (Volts)
Ammeter Change-Over Switch
Voltmeter Change-Over Switch
Voltage Regulator
3-Pole, 600 amp Main Circuit Breaker
“Control Box” (located behind the Gen. Control Panel)
Automatic Voltage Regulator
Diagnostic Display
Current Transformer
Over-Current Relay
Voltage Rectifer
Starter Relay
Engine Controller (Computer Controlled)
Voltage Change-over Board
Output Terminal Panel
The “Output Terminal Panel” is provided with the following:
Three 120/240V output receptacles (CS-6369), 50A
Three auxilliary circuit breakers, 50A
Two 120V output receptacles (GFCI), 20A
Two GFCI circuit breakers, 20A
Five output terminal lugs (3Ø power)
Battery Charger (Optional)
Water Heater (Optional)