Multiquip DCA-150SSKII Portable Generator User Manual


 
PAGE 32 DCA-150SSKII PARTS AND OPERATION MANUAL REV. #2 (05/08/01)
Circuit Breakers
To protect the generator from an overload, a 3-pole, 400 amp,
main
circuit breaker is provided to protect the UNV output
terminals from overload. In addition two single-pole, 20 amp
GFCI
circuit breakers are provided to protect the GFCI
receptacles from overload. Three 50 amp
load
circuit breakers
have also been provided to protect the load side of the
generator from overload. Make sure to switch
ALL
circuit
breakers to the "OFF" position prior to starting the engine.
OUTPUT TERMINAL PANEL FAMILIARIZATION
The Output Terminal Panel is provided with the following:
"
Three 240/139V output receptacles, 50 amp
"
Two 120V input receptacles, 20 amp
"
3 Load Circuit Breakers 265V @65 amps
"
2 Load GFCI Circuit Breakers 265V@ 20amps
Control Box
The Control Box is provided with the following:
"
Main Circuit Breaker 400 amps
"
Over-Current Relay
Output Terminal Panel
The Output Control Panel (See Figure 14) is located on the
right hand side (left from control panel) of the generator.
The UNV lugs are protected by a face plate cover that can
be secured in the close position by a pad lock. (See Figure
11).
120 Volt Recetacle
Two GFCI Duplex Nema 5-20R (120V, 20 Amp) recepacle is
provided on the output terminal. This receptacle can be
used anytime the generator is in operation. The receptacle
is controlled by the circuit breaker located on the control
panel.
Pressing the reset button resets the receptacle after being
tripped. Pressing the "Test Button" (See Figure 12) in the
center of this receptacle will check the GFCI function. The
receptacle should be tested at least once a month.
FIGURE 12. GFCI Test Button
FIGURE 11. Output Terminal Cover
Connecting Load
Loads can be connected to the generator by the UNV Lugs or
the convienience receptacles. (See figure 13). Make sure to
read the operation manual before attempting to connect a load
to the generator.
Maximum Output
The entire load connected to the UNV Lugs, all four slots in the
duplex receptacles, and the must not exceed 132 kW in
standby or 120 kW in prime output.
Twist Lock Dual Voltage Receptacles - To use these
receptacles, place the voltage selector switch in the single
phase 240/120 voltage position and adjust the output
voltage to 240 volts with the voltage regulator on the
Control Panel (see figure 14). Place the voltmeter change-
over switch to the U-W positon and the ammeter change-
over switch to the U or W to read the output.
FIGURE 13. Connecting Load
DCA-150SSKII OUTPUT TERMINAL PANEL OVERVIEW