Generac 6519 Portable Generator User Manual


 
Automatic Standby Generator Owner’s Manual 15
3.8.1— Main Circuit Breaker (Generator Disconnect)
This is a 2-pole breaker rated according to relevant specifications.
3.9 — Battery Charger
NOTE: The battery charger is integrated into the control panel. Battery Problem LED is illuminated when battery needs service.
The battery charger operates as a “Smart Charger” that ensures:
Output is continually optimized to promote maximum battery life.
Charging levels are safe.
3.10 — Setting the Exercise Timer
This generator is equipped with an exercise timer. Once it is set, the generator will star t and exercise every seven days, on the day of the week
and at the time of day specified. During this exercise period, the unit runs for approximately 12 minutes and then shuts down. Transfer of loads to
the generator output does not occur during the exercise cycle unless utility power is lost.
1. Place the generator in the AUTO mode.
2. Hold the “SET EXERCISE” Button for 3 seconds. The generator will start, run an exercise cycle and confirm the setting.
3. The exercise time is now established. The generator will exercise each week at this time.
To CHANGE the exercise time once it has been set, hold the “SET EXERCISE” button on the generator for three (3) seconds at the time you wish
the new exercise time to take place. The exercise timer does not correct for daylight savings time.
NOTE:
The exerciser
will
only work in the AUTO mode and
will default to exercise weekly at the time the Control Panel was last powered ON
unless this procedure is performed.
The exercise function
will
need
to
be reset every time the
12
volt battery and T1 power to the generator
are
disconnected
and then reconnected, and/or when the fuse
is removed and T1 power is removed from the generator.
NOTE: If the unit is equipped with Mobile Link