Alarm Clear Threshold: Determines how low the current load must drop in
order for the Alarm condition to be cancelled and for load shedding recovery
(if enabled) to occur. The Alarm Clear Threshold is entered as a percentage
of maximum capacity and is applied to both Over Current Branch Alarm
and Over Current Line Alarm (if present.) (Defaults: Initial Alarms = 70%;
Critical Alarms = 80%.)
Resend Delay: Determines how long the Outlet Managed PDU will wait to
resend an email message generated by this alarm, when the initial attempt to
send the notication was unsuccessful. (Default = 60 Minutes.)
Notify Upon Clear: When this item is enabled, the Outlet Managed PDU
will send additional notication when the situation that caused the alarm
has been corrected. For example, when Notify Upon Clear is enabled,
the Outlet Managed PDU will rst send notication when it detects that
current consumption has exceeded the trigger value, and then send a second
notication when it determines that the current consumption has fallen below
the trigger value. (Default = On.)
Email Message: Enables/Disables email notication for this alarm.
(Default = On.)
Note:
The Email Message parameter offers four different options: On, Off,
On (Copy to All Triggers) or Off (Copy to All Triggers). If either of
the "Copy to All Triggers" options is selected, then email notification
for all other alarms will be switched On or Off as indicated by this
parameter. For example, If "Off (Copy to All Triggers)" is selected,
then Email notification will be disabled for all other alarms too.
Address 1, 2, and 3: These parameters are used to select which of the three
email addresses dened via the "Email Messages" menu (see Section 5.9.11)
will receive the email alarm notication messages generated by this alarm.
The Address parameters can be used to select one, or any combination of the
addresses dened via the Email Messages menu. (Default = All On.)
Note:
If Email addresses have been previously defined, then the text
under the parameters will list the current, user selected email
addresses.