STANDBY PERMANENT - MOUNT SERIES GENERATOR
ELECTRICAL CONNECTION INFORMATION
High voltage may be present at receptacles and load studs while
engine is operating - DANGER of electrical shock is present.
Use extreme care.
Voltage is present at the 120V/15 Amp convenience receptacle only when generator is operating.
When configured for 277/480 main output, these receptacles
Will be delivering 139 VAC. Disconnection to avoid possible
equipment damage is suggested.
HARD WIRE LOAD TERMINAL BLOCK
1. Voltage available at load block is outlined in a chart below.
2. Cables must be brought into load block cabinet.
3. Do not start engine with load turned "on". Allow engine to come up to speed and warm
up first.
AVAILABLE VOLTAGE:
CONNECTION OF
GENERATOR LEADS
STUD
120/240 4 LEAD 1-2 = 240 VAC, 1 Phase
1-N, 2-N = 120 VAC, 1 Phase
277/480 High Wye 1-2-3 = 480 VAC, 3 Phase
1-N, 2-N, 3-N = 277 VAC, 1 Phase
120/240 Delta 1-2-3 = 240 VAC, 3 Phase
2-3 = 240 VAC, 1 Phase
1-N, 2-N, 3-N = 120 VAC, 1 Phase
120/208 Low Wye 1-2-3 = 208 VAC, 3 phase
2-3 = 208 VAC, 1 Phase
1-N, 2-N, 3-N = 120 VAC, 1 Phase