Baldor Generator Features
■
Baldor generators are manufactured in a certified
ISO9001 facility located in Oshkosh, Wisconsin
■
Every generator is design, prototype, and
production tested
■
Brushless synchronous four-pole alternator
■
Industrial grade exhaust silencer
■
Engine block heater
■
Baldor gensets attain one step load acceptance
of nameplate rating
■
PowerPAC 4 controller includes low oil pressure,
high coolant temperature, overspeed and overcrank
shutdowns with indicator lights
■
Flexible exhaust connection
■
■
Installation and operation manual
■
Worldwide network of parts and service
Ratings: - Standby Ratings: Standby ratings are applicable for supplying emergency power for the duration of a utility power outage. Primary power to the installation is
utility supplied. No overload capability for standby rating.Standby ratings in accordance with ISO 3046, BS55114, DIN 6271. Continuous Power Rating: Continuous
power is the maximum power available for continuous duty.A 10% overload capacity is available for 1 hour out of 12 hours of operation. Continuous Power ratings in
accordance with ISO 3046, BS55114, DIN 6271. For additional information, please consult factory.Manufacturer reserves the right to implement specifications or design
changes without notice. Single phase: Single phase units are rated at 1.0 (Unity) power factor.
Generator Ratings
150 C Rise 125 C Rise
Standby Rating Continuous Rating
Voltage PH Hz kW/kVA Amps kW/kVA Amps
120/240 1 60 130/130 541 117/117 487
110/220 1 50 108/108 490 97/97 441
Options
■
Exhaust silencer: Critical
■
Single wall sub base fuel tank
■
Double wall UL 142 approved sub base fuel
tank
■
Battery charger 12V float
■
Line circuit breaker
■
Flexible fuel lines
■
Weather protective enclosure
4 Cycle
Diesel Liquid Cooled
Standby Power Ratings
60Hz 50Hz
kW 130 108
kVA 130 108
Continuous Power Ratings
60Hz 50Hz
kW 117 97
kVA 117 97
Farm Duty 1-Phase Model: D130
Baldor
POWER SYSTEMS
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
Assembled in USA
Battery rack and cables