Baldor GLC30 Portable Generator User Manual


 
Operation 4-19MN2408
Figure 4-5 Main Menu Loop Parameters
Parameter Setting Range
System Voltage (Line To Line) XXXXX VAC 120–15000VAC
System Frequency 50Hz/60Hz Toggle Between 50/60 Hz
System Phases 1 Phase/3 Phase Toggle Between 1 & 3 Phase
y
Neutral Connected Toggle Between Yes/No
Voltage Sensing Voltage Sensing Pt Ratio
Ratio XXX Enter Number 1–208 (1=Direct)
Current Sensing Current Sensing Ct Ratio
Ratio XXX Enter Number 1–999 (1=Direct)
Temperature Scale Deg C/Deg F Toggle Between Deg C/Deg F
Pressure Scale PSI/KPA Toggle Between Psi/Kpa
Start Delay XXX Seconds 0–999 Seconds
Crank Time XX Seconds 0–99 Seconds
Rest Time XX Seconds 0–99 Seconds
Starter Re–engage Delay XX Seconds 0–99 Seconds 0=Disabled
Number Of Cranks XX Cranks 0–99 Times 0=Continuous
Bypass Delay XX Seconds 0–99 Seconds
Cool down Delay XX Seconds 0–9999 Seconds
Nominal RPM XXXX RPM 0–4000RPM
Flywheel Teeth (Engine Speed
Sensing, Magnetic Pick Up
XXX Teeth 0–999 Teeth
Crank Disconnect XX % 0–100%
Overspeed XX % 100–150%
Overspeed Transient X.X Seconds 0.0–9.9 Seconds
Run Output Fail Safe Yes/No Toggle Between Yes/No
Loss Of Speed Signal Shutdown Alarm/Shutdown Toggle Between Alarm/Shutdown
Common Fail For Not In Auto Yes/No Toggle Between Yes/No
Horn For Not In Auto Toggle Between Yes/No
Prog Output #1 Common Fail (Factory setting)
Prog Output #2 Common Fail (Factory setting)
Prog Output #3 Common Fail (Factory setting)
Prog Output #4 Common Fail (Factory setting)
Prog Output #5 Common Fail (Factory setting)
Prog Output #6 Common Fail (Factory setting)
Warm–up Delay 0–99 Seconds
Neutral Delay 0–99 Seconds
Return Delay 0–999 Seconds
Reset Run Hours Access by Master Password Only
Yes/No Toggle Between Yes/No