WARNING: An open bottom stationary engine generator set must be installed over noncombustible
materials and shall be located such that it prevents combustible materials from accumulating
under the generator set.
Several other factors should be carefully evaluated when selecting a location for installation:
1. For effective cooling and maintenance, the system should be mounted on a flat,
smooth, noncombustible level surface. A concrete pad is ideal and provides a secure
installation.
2. Installation should prevent water levels from reaching the generator. Drainage must be
adequate to keep concrete pad free from standing water.
3. Installation should prevent obstructions by buildup of leaves, grass, sand, snow, etc. If
these items pose a problem, consider building a small fence or other break to protect
the unit from accumulation of debris.
4. Installation should place the generator as close as possible to the fuel supply and
transfer switch.
5. At least forty–eight (48) inches clearance must be provided on all sides for air flow.
6. Access must be provided to allow the enclosure covers to be opened or removed for
service and maintenance.
7. Maximum Ambient temperature is 122"F (50"C).
Figure 3-2 Generator Mounting
A2
Electrical
Stub Up
B1
Fuel Stub Up
(All except GLC125)
B
A
A2 A1
F1 E1
B2
30
A
Fuel Stub Up
GLC125 ONLY
Large Exhaust Area
For GLC50, 60, 80, 100, 125 only
Table 3-3 Mounting Dimensions
Generator A A1 A2 B B1 B2 E1 F1
GLC30 78.0 6.0 33.0 44.0 42.5 6.25 17.0 32.0
GLC35 78.0 6.0 33.0 44.0 42.5 6.25 17.0 32.0
GLC45 78.0 6.0 33.0 44.0 42.5 6.25 17.0 32.0
GLC50 118.0 6.0 38.0 44.0 42.5 6.25 17.0 32.0
GLC60 118.0 6.0 38.0 44.0 42.5 6.25 17.0 32.0
GLC80 118.0 6.0 38.0 44.0 42.5 6.25 17.0 32.0
GLC100 118.0 6.0 38.0 44.0 42.5 6.25 17.0 32.0
GLC125 118.0 6.0 38.0 44.0 42.5 6.25 17.0 32.0