Remote/Auto Mode: This is the position you need to have the Master Control Switch set in
when you wish to operate the Generator Set automatically in conjunction with a Transfer
Switch. This way, the generator set can only be started by making a connection across the
remote start connection points on the terminal block located in the control box.
Should this remote start connection be opened up while the engine is running the engine will
shut down after a 60-90 second 'Cool Down' time delay.
The engine can be shut down immediately from this position by putting the Master Control
Switch into the 'OFF' position.
A fault condition will also shut the engine down immediately.
Fault Indicator Light:
This circular Red indicator light will come on in conjunction with the engine shutting down
whenever a fault condition develops.
One Fault Condition that will cause a shut down is if the engine's starter motor cranks for
more than 30 seconds without the engine starting. This fault shutdown is to prevent damage
to the starter motor.
Another Fault Condition will develop if the generator set stops producing power while the
engine is running. This fault shutdown is to prevent further potential damage to the generator
end itself.
Another Fault Condition will develop if the engine's Low Oil Pressure Protection System shuts
the engine down.
To reset the Control Logic once a Fault Condition has occurred, you must put the Master
Control Switch onto the 'OFF' position for a minimum of 10 seconds.
Fuse for the Control Logic Board:
This fuse is rated at 1 Amp. It's purpose is to prevent excessive and potentially damaging
current from getting to the circuit board.
Circuit Breaker:
The Circuit Breakers on the generator set provide overload protection for the generator set.
These Breakers protect the generator set against potential damage from excessive AC
current.