A SERVICE OF

logo

3
loca ted on the rear side of the unit, above the
evaporator/return air access panel. (See Fig. 1.)
To remove the filters:
1. Grasp the bottom flange of the upper panel.
2. Lift up and swing the bottom out unti l the panel dis-
engage s and pulls out.
3. Reach inside and extract the filters from the filter
rack.
4. Replace these filters as required with similar replace-
ment filters of same size.
To re--install the access panel:
1. Slide the top of the panel up under the unit top panel.
2. Slide the bottom into the side channels.
3. Push t he bottom flange down until it contacts the top
of the lower panel (or economizer top).
IMPORTANT: DO NOT OPERATE THE UNIT
WITHOUT THESE FILTERS!
Outside Air
Hood
Outside air hood inle t screens are permanent
aluminum--mesh type filters. Check these for cleanliness.
Remove the screens when cleaning is required. Clean by
washing with hot low--pressure water and soft detergent
and replace all screens before restarting the unit. Observe
the flow direction arrows on the side of each filter frame.
Economizer Inlet Air Screen
This air screen is retained by spring clips under the top
edge of the hood. (See Fig. 3.)
17 1/4ā€
DIVIDER
BAROMETRIC
RELIEF
CLEANABLE
ALUMINUM
FILTER
FILTER
HOOD
FILTE
R
CLIP
OUTSIDE
AIR
C06027
Fig. 3 -- Filter Installation
To remove the filter, open the spring clips. Re--install the
filter by placing the frame in its track, then closing the
spring clips.
Manual Outside Air Hood Screen
This inlet screen is secured by a retainer angle across the
top edge of the hood. (See Fig. 4.)
C07156
Fig. 4 -- Screens Installed on Outdoor--Air Hood
(Sizes 7--1/2 to 12--1/2 Tons Shown)
To remove the screen, loosen the screws in the top retainer
and slip the retainer up until the filter can be removed.
Re--install by placing the frame in its track, rotating the
retainer back down and tighten all screws.
C07087
Fig. 5 -- Belt Drive Motor Mounting
SUPPLY FAN (BLOWER) SECTION
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on the fan system, shut off all unit power and tag--out
the unit disconnect switch. Do not reach into the fan
section with power still applied to unit.
!
WARNING
Supply Fan (Belt--Drive)
The supply fan system consists of a forward--curved
centrifugal blower wheel on a solid shaft with two
concentric type bearings, one on each side of the blower
housing. A fixed --pitch driven pulley is attached to the fan
shaft and an adjustable--pitch driver pulley is on the
motor. The pulleys are connected using a ā€œVā€ type belt.
(See Fig. 5.)
Belt
Check the belt condition and tension quarterly. Inspect the
belt for signs of cracking, fraying or glazing along the
50TC