23
C08199
Fig. 33 -- P remi erLink Controller
PREMIERLINKT CONTROL
The PremierLink controller (see Fig. 33) is compatible
with Carrier Comfort Networkr (CCN) devices. This
control is designed to allow users the access and ability to
change factory--defined settings, thus expanding the
function of the standard unit control board. CCN service
access tools include System Pilot (TM), Touch Pilot (TM)
and Service Tool. (Standard t ier display tools Navigatort
and Scrolling Marquee are not suitable for use with latest
PremierLink controller (Version 2.x).)
The PremierLink control is factory--mounted in the 50TC
unit’s main control box to the left of the LCTB. Factory
wiring is completed through harnesses connected to t he
LVTB. Field connections are made at a 16--pole terminal
block (TB1) located on the bottom shelf of the unit
control box in front of the PremierLink controlle r The
factory-- installed PremierLink control includes the
supply--air te mperature (SAT) sensor. The outdoor air
temperature (OAT) sensor is included in the
FIOP/accessory Economizer 2 package.
Refer to Fig. 33 for PremierLink connection locations.
NOTE: Refer to Form 33CS--58SI for complete
PremierLink configuration, operating sequences and
troubleshooting information. Have a copy of this manual
available at unit start--up.
The PremierLink controller requires the use of a Carrier
electronic thermostat or a CCN connection for time
broadcast to initiate its internal timeclock. This is
necessary for broadcast of time of day functions
(occupied/unoccupied).
NOTE: PremierLink controller is shippe d in Sensor
mode. To be used with a thermostat, the PremierLink
controller must be configured to Thermostat mode. Refer
to PremierLink Configuration instructions for Operating
Mode.
Supply Air Temperature (SAT) Sensor — On
FIOP--equipped 50TC unit, the unit is supplied with a
supply--air tem perature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6--inches (12.7
mm) in length. It is a nominal 10--k ohm thermistor. See
Table 15 for temperature--resistance characteristic.
The SAT is factory--wired. The SAT probe is wire--tied to
the supply--air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installat ion.
Re--position the sensor in the flange of the supply--air
opening or in the supply air duct (as required by local
codes). Drill or punch a 1/2--in. hole in the flange or duct.
Use two field --supplied, self--drilling screws to secure the
sensor probe in a horizontal orientation. See Fig. 36.
SUPPLY AIR
RETURN AIR
SUPPLY AIR
TEMPERATURE
SENSOR
ROOF
CURB
C08200
Fig. 34 -- Typical Mounting Location for Supply Air
Temperature (SAT) Sensor on Small Rooftop Units
50TC