processed.
Check +/- VDC power supply outputs.
Check control wire harness integrity (Refer to the system schematic in Section 7).
Check CT harness for damage.
Check CT harness +/-15VDC at CT.
Check CT output voltage (mV) with reference to ground.
Replace CT showing high output voltage offset.
(9) Current Imbalance Fault (0x10000)
The PV-30208 has determined that there is an excessive phase-to-phase current imbalance, while the
system is operating.
Observe individual phase currents during operation with the operator interface program and with a
true RMS oscilloscope. Verify waveforms are sinusoidal and maintain proper phase relationships.
Determine which phase is imbalanced.
Verify phase conductor wiring integrity (Refer to the system schematic in Section 7).
Check CT control wire harness integrity (Refer to the system schematic in Section 7).
Replace CT on the phase exhibiting the current imbalance.
Stop Switch Fault
The on/off switch, located on the upper enclosure, is disabled. The contact block on the back of the
switch must be open for the PV-30208 to report this message.
If the switch is in the on position and the LCD reads ‘Stop Switch’:
Isolate the PV-30208 from external power (Refer to Section 2).
Verify continuity across the switch contact block while the switch is turned to the on position.
Verify continuity between J9-1 and J9-2 while the switch is enabled.