Xantrex Technology PV-30208 Portable Generator User Manual


 
SECTION 3
INSTALLATION AND INITIAL TURN-ON
PV-30208 Photovoltaic Inverter
Operation and Maintenance Manual
Copyright 2003, Xantrex Technology Inc.
DOCUMENT: 151315
3-5
The following wires for connecting the PV-30208 to external devices are not provided by Xantrex
Technology: (See wiring diagram on page 3-6.)
3-Phase 208 VAC inverter output to terminals of the 208 VAC primary side of isolation trans-
former. The neutral must be left floating. Ground loops will exist when the inverter starts
switching, which will cause the inverter to shut down due to phase over-currents and will
result in damage to the PV-30208. Also, insure that this neutral is not bonded to the isola-
tion transformer frame.
System electrical ground to the isolation transformer chassis ground.
Isolation transformer grid side terminals to line circuit breaker (or the AC disconnect switch if
present).
PV frame ground to PV-30208 enclosure chassis ground stud.
PV-30208 enclosure chassis ground stud to the electrical distribution system ground.
PV+ to the inverter enclosure terminal block TBDC+.
PV- to the inverter enclosure terminal block TBDC-.
PV neutral if connecting a bipolar PV array.
Install all wires listed above. Refer to the following wiring diagram and the system schematics in
Section 7 for more detailed terminal locations.