Sundance Spas 880 Series Hot Tub User Manual


 
14
Power Configurations for 780 Camden Models (North America,
60Hz)
This section describes the power configuration choices (Standard 50 Amp and Alternate
40 Amp) for Camden hot tub models.
Cong. #1
Standard 50A Configuration
(factory setting)
240 VAC/50A 3-wire configuration
(2 hots and a ground)
50A dual-pole GFCI breaker (hard
wired only)
Electrical current draw of 36A
In this Standard 50A configuration,
the heater does run if the jets pump is
running in high-speed.
Config. #2
Alternate 40A Configuration
(For homes where 240 VAC/50A power
is unavailable).
240 VAC/40A 3-wire configuration
(2 hots and a ground)
40A dual-pole GFCI breaker (hard
wired only)
Electrical current draw of 26A
If the home’s electrical system does
not have the full 240 VAC/50A, the spa
may be connected to a 240V/40A power
source after a qualified electrician makes
a minor circuit board modification.
In this configuration, the heater does
not run while the jets pump is running in
high-speed.
Note
Wire size must meet NEC recommendations and is determined by
maximum current draw and length or run.
Important:
All of the alternative electrical congurations require
a qualied technician to perform minor circuit board modications. To avoid
damage to the spa, do not activate power to the spa until these modications
have been made. We recommend Square-D or Cutler Hammer circuit
breakers.