Multiquip TLG-12SPX4 Portable Generator User Manual


 
TLG-12SPX4— OPERATION AND PARTS MANUAL — REV. #1 (12/17/09) — PAGE 29
1
Start-up
Procedure
1. Place engine throttle lever (Figure 22) in the START/IDLE
position (low speed).
2. Insert the ignition key into the ignition switch. Turn the
key to the RUN position and check to see that the Oil
Pressure light turns on (lights up). If it does not come on
check the lubrication oil system or check the light for
defective wiring. If light does turn on, then proceed to
step 2.
2. Turn the key clockwise to the PRE-HEAT position (Figure
23A) and observe the Pre-Heat Lamp. When the Pre-
Heat Lamp has turned off, continue turning the ignition
key clockwise to the START position (Figure 23B). When
the engine starts, release the key and allow it to return to
the RUN position. If engine fails to start within 10 seconds,
wait 30 seconds and repeat this step.
Figure 23. Ignition Switch
TLG-12SPX4 — GENERATOR START-UP PROCEDURE
The engine's exhaust contains harmful emissions.
ALWAYS have adequate ventilation when operating
.
Direct exhaust away from nearby personnel.
Before Starting
1. Place main circuit breaker (Figure 20) on the controll
panel in the OFF position prior to starting the engine.
Figure 20. Main Circuit Breaker (OFF)
3. Connect the load to the
receptacles
as shown in Figure
11. These load connection points can be found on the
output terminal panel and the output terminal panel’s hard
wire hookup panel.
CAUTION - LETHAL EXHAUST HAZARD
3. Let it idle for 3-5 minutes listen and check for any
abnormal sounds or smells. If any abnormalities exists
shutdown the engine and correct the problem.DO NOT
RUN GENERATOR AT HIGH SPEED OPERATION
IMMEDIATELY AFTER STARTING
4. When the engine starts, the Oil Pressure Light should
go out. If the light stays on, stop the engine and check
lubricating oil system.
NEVER!
manually start the engine with the
main
,
GFCI
or
auxiliary
circuit breakers in the ON (closed) position.
WARNING - STARTING THE GENERATOR
NOTE
Figure 21. Engine Enclosure Doors
Generator may not be equipped with
auxiliary circuit breakers or
receptacles. This feature is optional
4. Close all engine enclosure doors (Figure 21).
Figure 22.Throttle Lever (Low Speed)