DCA800SSK2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (09/03/09) — PAGE 35
GENERATOR STARTUP PROCEDURE (MANUAL)
Press the 14. main circuit breaker "ON" switch (Figure 52).
Main Circuit Breaker ON SwitchFigure 52.
Verify that the main circuit breaker "15. ON" lamp (Figure 53)
is lit (ON).
Main Circuit Breaker ON LampFigure 53.
Place the three 16. auxiliary circuit breakers in the ON
position (Figure 54).
Main, Aux. and GFCI Figure 54.
Circuit Breakers (ON)
Verify that the generator’s ammeter (Figure 55) reads 17.
the anticipated amount of current with respect to the
load. The ammeter will only display a current reading
if a load is in use.
Ammeter (Load)Figure 55.
The generator will run until manually stopped or an 18.
abnormal condition occurs.
Ammeter (No Load)Figure 48.
The engine oil pressure gauge (Figure 49) will indicate 11.
the oil pressure of the engine. Under normal operating
conditions the oil pressure is approximately 28 to 85
psi. (193~586 kPa).
Oil Pressure GaugeFigure 49.
The 12. coolant temperature gauge (Figure 50) will
indicate the coolant temperature. Under normal
operating conditions the coolant temperature should
be between 167°~203°F (75°~95°C) (Green Zone).
Coolant Temperature GaugeFigure 50.
The13. tachometer gauge (Figure 51) will indicate the
speed of the engine when the generator is operating.
Under normal operating conditions this speed is
approximately 1800 RPM’s.
Engine Tachometer GaugeFigure 51.