DCA-220SSJ/SSJU— OPERATION AND PARTS MANUAL — REV. #1 (01/06/09) — PAGE 45
1
Maximum Amps
Table 10 shows the
maximum
amps the generator can pro-
vide. DO NOT exceed the maximum amps as listed.
How to Read the Output Terminal Gauge.
The AC ammeter and AC voltmeter change-over switches
on the control panel DO NOT effect the generator output.
They are provided to help observe how much power is being
supplied, produced at the UVWO terminals lugs.
When the voltage change-over board (Figure 16) is jumpered
for 3Ø, 240V operation place the
AC Voltmeter Change-
Over
Switch
(Figure 17) to the W-U position and the
AC
Ammeter Change-Over Switch
(Figure 19) to the U or W
position. Use the AC voltmeter or AC ammeter (Figures 18
and 20) to read the output on the selected leg of the UVWO
terminals.
Figure 17. AC Voltmeter
Change-Over Switch
Figure 18. AC Voltmeter Gauge
(Volt reading on W-U Lug)
Figure 20. AC Ammeter
(Amp reading on U lug)
Figure 19. AC Ammeter
Change-Over Switch
The
ammeter
gauge will only
show a reading when the
Output Terminal Lugs
are
connected to a load and in use.
NOTE
DCA-220SSJ/SSJU — GENERATOR OUTPUTS/ GAUGE READING
Table 10. Generator Maximum Amps
Model DCA-220SSJ/SSJU
Rated Voltage Maximum Amps
Single Phase
100 Volt
466 amps (4 wire)
Single Phase
200 Volt
233 amps (4 wire)
Three Phase
200 Volt
508 amps
Three Phase
400 Volt
254 amps