DCA-220SSJ/SSJU — GENERATOR OUTPUTS
Generator Amperage
Tables 8 and 9 describe the generator’s current output capa-
bility for both 1Ø-phase and 3Ø phase applications.
Generator Output Voltages
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by apply-
ing jumpers (6) to the
voltage change-over board
(Figure 15).
To obtain some of the voltages as listed in Table 6 (see
below) will require a fine adjustment using the
voltage regu-
lator
(VR)
control knob
located on the control panel.
Voltage Change-Over Board
The
voltage change-over board
(Figure 16) is located on
the control box, behind the generator control panel. This
board has been provided for ease of voltage selection.
CAUTION - CHANGING VOLTAGES
NEVER attempt to place jumper plates on the
voltage
change-over board
while the generator is in operation.
There exist the possibility of
electrocution, electrical
shock or burn, which can cause severe bodily harm
or even death
!
Figure 16. Voltage Change-Over Board
Table 7. Voltages Available
Three Phase
(Switchable)
200V 220V 400V 440V
Single Phase
(Switchable)
115V 127V 230V 254V
Table 8. Generator Ampere Ratings — 1Ø
kW 100V 200V
16 160 80
36 360 180
56 560 280
76 760 380
96 960 480
116 1160 580
136 1360 680
156 1560 780
176 (Max) 1760 880
Table 9. Generator Ampere Ratings — 3Ø
KVA 200V 400V
20 57 29
36 103 51
56 161 80
68 196 98
100 288 144
120 346 173
144 415 207
176 508 254