PAGE 40 — DCA-220SSJ/SSJU— OPERATION AND PARTS MANUAL — REV. #1 (01/06/09)
Output Terminal Familiarization
The “
Output Terminal Panel
” (Figure 8) is provided with the
following:
■■
■■
■
Three (3) 100/200V output receptacles @ 50 amp
■■
■■
■
Three (3) Circuit Breakers @ 50 amps
■■
■■
■
Two (2) 100V GFCI receptacles @ 20 amp
■■
■■
■
Two (2) GFCI Circuit Breakers @ 20 amps
■■
■■
■
Five (5) Output Terminal Lugs ( U, V, W, O, Ground)
Output Terminal Panel
The
Output Terminal Panel
(Figure 9) shown below is located
on the right-hand side (left from control panel) of the generator.
Lift up on the cover to gain access to receptacles and terminal
lugs.
NOTE
Terminal legs “O” and “Ground”
are considered
bonded grounds
.
Figure 9. Output Terminal Panel
DCA-220SSJ/SSJU — OUTPUT TERMINAL PANEL FAMILIARIZATION
AUX. POWER RECEPTACLES
100/200V, 50AMPS
100 VAC, 20AMP
GFCI RECEPTACLES
Y
X
W
CS-6369
TWIST-LOCK
CIRCUIT BREAKERS
FOR GFCI RECEPTACLES
RECEPTACLE
AND
CIRCUIT BREAKER
PANEL
M
Q
P
O
W
E
R
ACCESS DOOR
LIFT TO OPEN
HARD WIRE
HOOKUP PANEL
O
U
V
W
BLACK RED BLUE WHITE GREEN
1ØAND 3Ø,
480 -120 VAC
OUTPUT TERMINALS
NEUTRAL
TERMINAL
GROUND
TERMINAL
CIRCUIT BREAKERS
FOR CS-6369 TWIST
LOCK RECEPTACLES