PAGE 30 — DCA-10SPX4— OPERATION AND PARTS MANUAL — REV. #0 (02/17/09)
DCA-10SPX4 — GENERATOR START-UP PROCEDURE
Figure 29. Voltage Adjust Control Knob
Figure 28. Voltmeter
Figure 27. Main, GFCI, and Aux.
Circuit Breakers (ON)
7. Place the
main
,
GFCI
, and
aux
. (Figure 27) circuit breakers
on the control panel in the ON position.
12. Observe the generator's ammeter (Figure 30) and verify
it reads the anticipated amount of current with respect
to the load. The ammeter will only display a current
reading if a load is in use.
Figure 30. Ammeter (Load)
13. The generator will run until manually stopped or an
abnormal condition occurs.
Figure 25. Ammeter (No Load)
5. The ammeter (Figure 25) will indicate
zero amps
with
no load applied. When a load is applied, the ammeter
will indicate the amount of current that the load is
drawing from the generator.
6. Set the Speed Control Switch to the RUN position
(Figure 26).
8. The generator's AC-voltmeter (Figure 28) will display the
generator’s output in VOLTS. If the voltage is not within
the specified tolerance, use the voltage adjustment
control knob (Figure 29) to increase or decrease the
desired voltage.
Figure 26. Speed Control Switch (RUN)