Cleaning the Fuel Filter
Every 100 hours: Clean fuel fi lter every 100 hours of
operation or once a month to remove dust or water.
1. Place fuel cock lever (Figure 32) in the close position.
2. Disconnect fuel lines from fuel fi lter.
Figure 32. Fuel Cock Lever (OFF)
Replacing Fuel Filter Element
Every 200 hours: Replace fuel fi lter element.
1. Remove the top cap (Figure 33) from the fuel fi lter and
rinse cap and fi lter bowl with diesel fuel.
2. Remove element, and rise with diesel fuel.
3. Reinstall fuel fi lter and connect fuel lines.
Figure 33. Fuel Filter Disassembly
4. Inspect all fuel lines every 50 hours.
MAINTENANCE
Radiator
Check Daily: Always check the level of the coolant in the
radiator before starting the engine. Remove the radiator
cap and verify that the coolant reaches top of radiator coils.
1. DO NOT remove the radiator cap while the coolant is
hot. The possibility exists of severe burns or scalding
from the coolant gushing out. Let the coolant cool
before removing radiator cap.
2. Check coolant in the reserve tank daily (Figure 34).
Make sure the level is between the FULL (H) and LOW
(L) markings. Fill reserve tank with a mixture of 50/50
antifreeze/water.
Figure 34. Radiator/Reserve Tank
Flushing Out Radiator and Replacing Coolant
1. Remove radiator coolant plug (Figure 35) located at
the bottom of the generator enclosure and drain
radiator coolant. Open the radiator cap while draining.
Remove the overfl ow tank and drain.
Figure 35. Coolant Drain Plug
OIL DRAIN
COOLANT DRAIN
COOLANT DRAIN
PLUG